PIM-430 Series Protectowire Dual Input Interface Module
The PIM-430 is a detection module that interfaces between a main control panel detection circuit(s) or addressable node(s)
and Protectowire Linear Heat Detector. The module may be configured to provide two (2) Class B (Style B) alarm initiating
circuits each capable of operating up to 2,000m (6,560 ft.) of Protectowire Linear Heat Detector or one (1) 3-wire Class B
(Style B) dual input initiating circuit capable of operating up to 2,000m (6,560 ft.) of Protectowire Type TRI (TRI-WireTM).
The PIM-430 initiating circuits are also compatible with other types of normally open non-resistive contact devices.